Resolution MSC.265(84)
AMENDMENTS TO THE REVISED GUIDELINES FOR APPROVAL OF SPRINKLER SYSTEMS
EQUIVALENT TO THAT REFERRED TO IN SOLAS REGULATION II-2/12
(RESOLUTION A.800(19))
(adopted on 9 May 2008)
amended
by MSC 84/24/Add.2/Corr.1 15 October 2008
THE
MARITIME SAFETY COMMITTEE,
RECALLING
Article 28(b) of the Convention on the International Maritime Organization
concerning the functions of the Committee,
NOTING
the significance of the performance and reliability of the sprinkler systems
approved under provisions of regulation II-2/12 of the International Convention
for the Safety of Life at Sea (SOLAS), 1974,
DESIROUS
of keeping abreast of the advancement of sprinkler technology and further
improving fire protection on board ships,
HAVING
CONSIDERED, at its eighty-fourth session, the text of the proposed amendments
to the Revised Guidelines for approval of sprinkler systems equivalent to that
referred to in SOLAS regulation II-2/12 (resolution A.800(19)),
1.
ADOPTS the amendments to the Revised Guidelines for approval of sprinkler
systems equivalent to that referred to in SOLAS regulation II-2/12 (resolution
A.800(19)), the text of which is set out in the annex to the present
resolution;
2.
INVITES Governments to apply the amendments when approving equivalent sprinkler
systems on or after 9 May 2008.
Annex.
AMENDMENTS TO THE REVISED GUIDELINES FOR APPROVAL OF SPRINKLER SYSTEMS
EQUIVALENT TO THAT REFERRED TO IN SOLAS REGULATION II-2/12 (RESOLUTION
A.800(19))
1.
The following new section 1-1 is added after the existing section 1:
1-1.1
The present Guidelines apply to equivalent sprinkler systems installed on or
after 9 May 2008.
1-1.2
Existing type approvals issued to confirm compliance of equivalent sprinkler
systems with the Revised Guidelines, adopted by resolution A.800(19), should
remain valid until 6 years after 1 July 2009.
1-1.3
Existing equivalent sprinkler systems installed before 9 May 2008, based on
resolution A.800(19), should be permitted to remain in service as long as they
are serviceable."
3. PRINCIPAL REQUIREMENTS FOR THE SYSTEM
2.
The existing paragraph 3.3 is replaced by the following:
"3.3 The
sprinkler system should be capable of continuously supplying the water-based
extinguishing medium for a minimum of 30 min. A pressure tank or other means
should be provided to meet the functional requirement stipulated in the FSS
Code, chapter 8, paragraph 2.3.2.1. The design of the system should ensure that
full system pressure is available at the most remote nozzle in each section
within 60 s of system activation."
3.
The existing paragraphs 3.8 and 3.9 are replaced by the following:
"3.8
There should be not less than two sources of power for the system. Where the
sources of power for the pump are electrical, these should be a main generator
and an emergency source of power. One supply for the pump should be taken from
the main switchboard, and one from the emergency switchboard by separate
feeders reserved solely for that purpose. The feeders should be so arranged as
to avoid galleys, machinery spaces and other enclosed spaces of high fire risk
except in so far as it is necessary to reach the appropriate switchboards, and
should be run to an automatic changeover switch situated near the sprinkler
pump. This switch should permit the supply of power from the main switchboard
so long as a supply is available there from, and be so designed that upon
failure of that supply it will automatically change over to the supply from the
emergency switchboard. The switches on the main switchboard and the emergency
switchboard should be clearly labelled and normally kept closed. No other
switch should be permitted in the feeders concerned. One of the sources of
power supply for the system should be an emergency source. Where one of the
sources of power for the pump is an internal combustion engine, it should, in
addition to complying with the provisions of the FSS Code, chapter 8, paragraph
2.4.3, be so situated that a fire in any protected space will not affect the
air supply to the machinery. Pump sets consisting of two diesel engines each
supplying at least 50% of the required water capacity are considered acceptable
if the fuel supply is adequate to operate the pumps at full capacity for a
period of 36 h on passenger ships and 18 h on cargo ships.
3.9
The system should be provided with a redundant means of pumping, including
drivers, or otherwise supplying a water-based extinguishing medium to the
sprinkler system. The capacity of the redundant means should be sufficient to
compensate for the loss of any single supply pump or alternative source.
Failure
of any one component in the power and control system should not result in a
reduction of the automatic release capability or reduction of sprinkler pump
capacity by more than 50%. Hydraulic calculations should be conducted to assure
that sufficient flow and pressure are delivered to the hydraulically most
remote 140 m2 in the event of the failure of any one
component."
4.
The existing paragraph 3.13 is replaced by the following:
"3.13 Each
section of sprinklers should be capable of being isolated by one stop valve
only. The stop-valve in each section should be readily accessible in a location
outside of the associated section or in cabinets within stairway enclosures.
The valves location should be clearly and permanently indicated. Means should
be provided to prevent the operation of the stop-valves by an unauthorized
person. Isolation valves used for service, maintenance or for refilling of
antifreeze solutions may be installed in the sprinkler piping in addition to
the section stop valves, if provided with a means for giving a visual and
audible alarm as required by paragraph 3.17. Valves on the pump unit may be
accepted without such alarms if they are locked in the correct position."
5.
The existing paragraph 3.15 is replaced by the following:
"3.15 The
sprinkler system water supply components should be outside category A machinery
spaces and should not be situated in any space required to be protected by the
sprinkler system."
6.
The existing paragraph 3.19 is replaced by the following:
"3.19
Installation plans and operating manuals should be supplied to the ship and be
readily available on board. A list or plan should be displayed showing the
spaces covered and the location of the zone in respect of each section.
Instructions for testing and maintenance should also be available on board. The
maintenance instructions should include provisions for a flow test of each
section at least annually to check for possible clogging or deterioration in
the discharge piping."
7.
The existing paragraph 3.22 is replaced by the following:
"3.22
Pumps and alternative supply components should be capable of supplying the
required flow rate and pressure for the space with the greatest hydraulic
demand. For the purposes of this calculation, the design area used to calculate
the required flow and pressure should be the deck area of the most
hydraulically demanding space, separated from adjacent spaces by A-class
divisions. The design area need not exceed 280 m2. For application
to a small ship with a total protected area of less than 280 m2, the
Administration may specify the appropriate area for sizing of pumps and
alternate supply components."
3.23
The nozzle location, type of nozzle, and nozzle characteristics should be
within the tested limits determined by the fire test procedures in appendix 2
to provide fire control or suppression as referred to in paragraph 3.2.
3.24
For atriums with intermediate level deck openings exceeding 100 m2,
ceiling mounted sprinklers are not required.
3.25
The system should be designed in such a way that during a fire occurrence, the
level of protection provided to those spaces unaffected by fire is not reduced.
3.26
A quantity of spare water mist nozzles should be carried for all types and
ratings installed on the ship as follows:
|
Total number of nozzles |
Required number of spares |
|
< 300 300 to 1000 > 1000 |
6 12 24 |
The
number of spare nozzles of any type need not exceed the total number of nozzles
installed of that type.
3.27
Any parts of the system which may be subjected to freezing temperatures in
service should be suitably protected against freezing."
Appendix 1.
COMPONENT MANUFACTURING STANDARDS FOR WATER MIST NOZZLES
8.
In appendix 1, a new paragraph 5.21.4 is added as follows:
"5.21.4
Alternative supply arrangements to the apparatus shown in figure 3 may be used
where damage to the pump is possible. Restrictions to piping defined by note 2
of table 5 should apply to such systems."
Appendix 2.
FIRE TEST PROCEDURES FOR EQUIVALENT SPRINKLER SYSTEMS IN ACCOMMODATION, PUBLIC
SPACE AND SERVICE AREAS ON PASSENGER SHIPS
9.
The existing title and the text of appendix 2 are replaced by the following:
"Appendix 2.
FIRE TEST PROCEDURES FOR WATER MIST
SYSTEMS IN ACCOMMODATION, PUBLIC
SPACES AND SERVICE AREAS ON PASSENGER SHIPS
1.1
These test procedures describe a fire test method for evaluating the
effectiveness of water mist systems equivalent to systems covered by chapter 8
of the FSS Code in accommodation and service areas on board ships. It should be
noted that the test method is limited to the systems effectiveness against
fire and is not intended for testing of the quality and design parameters of
the individual components of the system.
1.2
In order to fulfil the requirements of paragraph 3.5 of the Guidelines, the
system should be capable of fire control or suppression in a wide variety of
fire loading, fuel arrangement, room geometry and ventilation conditions.
1.3
Products employing materials or having forms of construction differing from the
requirements contained herein may be examined and tested in accordance with the
intent of the requirements and, if found to be substantially equivalent, may be
judged to comply with this document.
1.4
Products complying with the text of this document will not necessarily be
judged to comply, if, when examined and tested, they are found to have other
features which impair the level of safety contemplated by this document.
2. Hazard and occupancy classification
For
the purposes of identifying the different fire risk classifications, table 1 is
given, which correlates the fire tests with the classification of occupancy
defined in SOLAS regulations II-2/9.2.2.3 and II-2/9.2.2.4:
Table 1
Correlation between fire tests with the classification of occupancy defined in SOLAS regulations II-2/9.2.2.3 and 9.2.2.4
|
|
Corresponding fire test |
|||
|
Occupancy classification |
Section 5 cabin |
Section 5 corridor |
Section 6 public spaces |
Section 8 storage |
|
(1)
Control stations |
|
|
X |
|
|
(2)
Stairways |
|
X1 |
|
|
|
(3)
Corridors |
|
X1 |
|
|
|
(6)
Accommodation spaces of minor fire risk |
X2 |
|
X3 |
|
|
(7)
Accommodation spaces of moderate fire risk |
X2 |
|
X3 4 |
|
|
(8)
Accommodation spaces of greater fire risk |
|
|
X3 4 |
|
|
(9)
Sanitary and similar spaces |
X2 |
|
X 3 |
|
|
(11)
Refrigerated chambers |
|
|
X |
|
|
(12)
Main galleys and annexes |
|
|
X |
|
|
(13)
Store rooms, workshops, pantries, etc. |
|
|
|
X |
|
(14)
Other spaces in which flammable liquids are stowed |
|
|
|
X |
Notes:
1 For corridors and stairways
wider than 1.5 m, use section 6 public space fire test instead of the corridor
fire test.
2 For spaces up to the area of
the cabin applied in tests of section 5.
3 For spaces over the area of
the cabin applied in tests of section 5.
4 Refer to annex, item 3.24.
3.1
Fire suppression: sharply reducing the heat release rate of a fire and
preventing its re-growth by means of a direct and sufficient application of
water through the fire plume to the burning fuel surface.
3.2
Fire control: limiting the size of a fire by distribution of water so as to
decrease the heat release rate and pre-wet adjacent combustibles, while
controlling ceiling gas temperatures to avoid structural damage.
3.3
Fire source: fire source is defined as the combustible material in which the
fire is set and the combustible material covering walls and ceiling.
3.4
Igniter: the device used to ignite the fire source.
The
fire test procedures are intended for pressurized wet-pipe systems with
individually activated (automatic) nozzles.
Water
without any fire-extinguishing additives should be used, unless the additives
have been approved for fire protection service by an independent authority. The
approval of the additives should consider possible adverse health effects to
exposed personnel, including inhalation toxicity.
These
test procedures are applicable to either overhead nozzles installed on the
ceiling, or sidewall nozzles installed on bulkheads below the ceiling. Separate
approval tests should be conducted for each nozzle type.
The
testing organization should be responsible for assuring that the nozzles for
each fire test are installed in accordance with the manufacturers design and
installation instructions. The tests should be performed at the maximum
specified spacings, installation height and distances below the ceiling. In
addition, if the testing organization finds it necessary, selected fire tests
should also be conducted at minimum specified spacings, installation height and
distances below the ceiling. Where two types of nozzles are installed in the
same area, an overlap of the different nozzle spray patterns should be provided
equal to at least one half of the maximum approved nozzle spacing.
4.2
Water pressure and flow rates
The
testing organization should be responsible for assuring that all fire tests are
conducted at the operating pressure and flow rates specified by the
manufacturer.
For
all tests, the system should either be:
.1 pressurized
to the minimum operating pressure specified by the manufacturer. Upon
activation of the first nozzle, the flowing water pressure should be maintained
at the minimum system operating pressure; or
.2 pressurized
to the minimum stand-by pressure specified by the manufacturer. Upon activation
of the first nozzle, the flowing water pressure should be gradually increased
to the minimum system operating pressure, specified by the manufacturer. The
delay time until the minimum system operating pressure is reached should be at
least 15 s. The delay time recorded during the tests should be documented and
included in the approval of the system.
Temperatures
should be measured as described in detail under each chapter. Chromelalumel
thermocouple wires not exceeding 0.5 mm in diameter welded together should be
used. The temperatures should be measured continuously, at least every 2 s,
throughout the tests.
4.4
Fire test hall and environmental conditions
The
fire tests are to be conducted inside a well-ventilated fire test hall, in
order to minimize enclosure effects affecting the outcome of the testing. The
enclosure effects include accumulation of heat, smoke and water droplets within
the test area.
The
fire test hall should have an ambient temperature of 20 5C at the start of
each test. Standing water should not be permitted on the floor of the test hall
at the start of each test. The suspended ceiling should be dry at the start of
each test.
Details
of the fire test hall geometry, the ventilation conditions as well as of the
environmental conditions with respect to the above should be given in the fire
test report.
Unless
otherwise stated, the following tolerances should apply:
.1 length 2% of value;
.2 volume 5% of value;
.3 pressure 3% of value; and
.4 temperature
5% of value. These tolerances are in accordance with ISO Standard 6182-1:1994.
The
following observations should be made during and after each test: .1 time of
ignition; .2 activation time of each nozzle; .3 time when water flow is shut
off; .4 damage to the fire source; .5 temperature recordings; .6 system flow
rate and pressure; and .7 total number of operating nozzles.
If
the requirements for fire sources specified in the following sections of this
test method cannot be fulfilled, it is the responsibility of the test
laboratory to show that alternative materials used have burning characteristics
similar to those of specified materials.
4.8
Product and documentation requirements
The
fire test report should identify the critical parameters to be incorporated
into the design, installation and operating instruction manual. The instruction
manual should reference the limitations of each device and should include at
least the following items:
.1 description
and operating details of each device and all accessory equipment, including
identification of extinguishing system components or accessory equipment by
part or model number;
.2 nozzle design
recommendation and limitations for each fire type;
.3 type and
pressure rating of pipe, tubing and fittings to be used;
.4 equivalent
length values of all fittings and all system components through which water
flows;
.5 discharge
nozzle limitations, including maximum dimensional and area coverage, minimum
and maximum installation height limitations, and nozzle permitted location in
the protected volume;
.6 range of
filling capacities for each size storage container;
.7 details for
the proper installation of each device, including all component equipment;
.8 reference to
the specific types of detection and control panels (if applicable) to be
connected to the equipment;
.9 operating
pressure ranges of the system;
.10 method of
sizing pipe or tubing;
.11 recommended
orientation of tee fittings and the splitting of flows through tees; and
.12 maximum
difference in operating (flowing) pressure between the hydraulically closest
and most remote nozzle.
5.1.1
The fire tests should be conducted in a 3 m x 4 m, 2.5 m high cabin connected
to the centre of a 1.5 m x 12 m long corridor, 2.5 m high with both ends open.
The cabin area may be increased up to the maximum size to be protected with one
nozzle. The disabled nozzle test should be conducted in a 3 m x 4 m cabin.
5.1.2
The cabin should be fitted with one doorway opening, 0.8 m wide and 2.2 m high,
which provides for a 0.3 m lintel above the opening.
5.1.3
The walls of the cabin should be constructed from an inner layer of nominally
12 mm thick non-combustible wall board with a nominally 45 mm thick mineral
wool liner. The walls and ceiling of the corridor and ceiling of the cabin
should be constructed of nominally 12 mm thick non-combustible wall boards. The
cabin may be provided with a window, having a maximum area of 1 m2,
in the wall opposite the corridor for observation purposes during the fire
tests.
5.1.4
The cabin and corridor ceiling should be covered with cellulosic acoustical
panels. The acoustical panels should be nominally 12 mm to 15 mm thick and
should not ignite when tested in