MEPC.244(66) 2014 Standard specification for shipboard incinerators

RESOLUTION MEPC.244(66)

Adopted on 4 April 2014

 

2014 STANDARD SPECIFICATION FOR SHIPBOARD INCINERATORS

 

 

THE MARINE ENVIRONMENT PROTECTION COMMITTEE,

 

RECALLING Article 38(a) of the Convention on the International Maritime Organization concerning the function of the Marine Environment Protection Committee (the Committee) conferred upon it by international conventions for the prevention and control of marine pollution from ships,

 

RECALLING ALSO that, at its fortieth session, the Committee adopted, by resolution MEPC.76(40), the Standard specification for shipboard incinerators, in respect of regulation 16.6.1 and appendix IV to MARPOL Annex VI,

 

NOTING that, at its forty-fifth session, the Committee adopted, by resolution MEPC.93(45), Amendments to the standard specification for shipboard incinerators,

 

NOTING ALSO that, at its sixty-fourth session, the Committee decided that incinerators with a capacity greater than 1,500 kW and up to 4,000 kW can be type-approved under the existing standard specification for shipboard incinerators,

 

BEING AWARE of the need to update the definition section, as well as references to the SOLAS Convention and IEC standards in the Standard specification for shipboard incinerators,

 

HAVING CONSIDERED, at its sixty-sixth session, the 2014 Standard specification for shipboard incinerators,

 

1. ADOPTS the 2014 Standard specification for shipboard incinerators, as set out in the annex to the present resolution;

 

2. INVITES Administrations to take the annexed Standard specification into account when certifying a shipboard incinerator;

 

3. INVITES Governments to note that, taking into account regulation 16.5.2 of MARPOL Annex VI, the standard specification for shipboard incinerators does not apply to the design, installation and operation of alternative designs of shipboard thermal waste treatment devices including those which use thermal processes to convert ship generated wastes to gas;

 

4. REQUESTS the Parties to MARPOL Annex VI and other Member Governments to bring the annexed standard specification to the attention of shipowners, ship operators, shipbuilders, manufacturers of shipboard incinerators and any other interested groups;

 

5. SUPERSEDES the Standard specification for shipboard incinerators adopted by resolution MEPC.76(40), as amended by resolution MEPC.93(45).

 

ANNEX

 

2014 STANDARD SPECIFICATION FOR SHIPBOARD INCINERATORS

 

Table of contents

 

1 Scope

 

2 Definitions

 

3 Materials and manufacture

 

4 Operating requirements

 

5 Operating controls

 

6 Other requirements

 

7 Tests

 

8 Certification

 

9 Marking

 

10 Quality assurance

 

 

Annex 1

Emission standard for shipboard incinerators with capacities of up to 4,000 kW

Annex 2

Fire protection requirements for incinerators and waste stowage spaces

Annex 3

Incinerators integrated with heat recovery units

Annex 4

Flue gas temperature

Annex 5

Form of IMO type aproval certificate for shipboard incinerators with capacities of up to 4,000 kW

1 SCOPE

 

1.1 The 2014 Standard specification for shipboard incinerators (the Specification) covers the design, manufacture, performance, operation and testing of incinerators intended to incinerate garbage and other shipboard wastes generated during the ship's normal service.

 

1.2 This Specification applies to those incinerator plants with capacities up to 4,000 kW per unit.

 

1.3 This Specification does not apply to systems on special incinerator ships, e.g. for burning industrial wastes such as chemicals, manufacturing residues, etc.

 

1.4 This Specification does not address the electrical supply to the unit, nor the foundation connections and stack connections.

 

1.5 This Specification provides emission requirements in annex 1, and fire protection requirements in annex 2. Provisions for incinerators integrated with heat recovery units and provisions for flue gas temperature are given in annex 3 and annex 4, respectively.

 

1.6 This Specification may involve hazardous materials, operations, and equipment. It does not purport to address all of the safety problems associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use, including possible port State limitations.

 

2 DEFINITIONS

 

For the purpose of the Specification, the following definitions apply:

 

2.1 Ship means a vessel of any type whatsoever operating in the marine environment and includes hydrofoil boats, air-cushioned vehicles, submersibles, floating craft and fixed or floating platforms.

 

2.2 Shipboard incinerator or incinerator means a shipboard facility designed for the primary purpose of incineration.

 

2.3 Garbage means all kinds of food wastes, domestic wastes and operational wastes, all plastics, cargo residues, incinerator ashes, cooking oil, fishing gear, and animal carcasses generated during the normal operation of the ship and liable to be disposed of continuously or periodically except those substances which are defined or listed in Annexes to MARPOL. Garbage does not include fresh fish and parts thereof generated as a result of fishing activities undertaken during the voyage, or as a result of aquaculture activities which involve the transport of fish including shellfish for placement in the aquaculture facility and the transport of harvested fish including shellfish from such facilities to shore for processing.

 

2.4 Waste means useless, unneeded or superfluous matter which is to be discarded.

 

2.5 Food wastes means any spoiled or unspoiled food substances and includes fruits, vegetables, dairy products, poultry, meat products and food scraps generated aboard ship.

 

2.6 Plastic means a solid material which contains as an essential ingredient one or more high molecular mass polymers and which is formed (shaped) during either manufacture of the polymer or the fabrication into a finished product by heat and/or pressure. Plastics have material properties ranging from hard and brittle to soft and elastic. For the purposes of this specification, plastic means all garbage that consists of or includes plastic in any form, including synthetic ropes, synthetic fishing nets, plastic garbage bags and incinerator ashes from plastic products.

 

2.7 Domestic wastes means all types of wastes not covered by Annexes to MARPOL that are generated in the accommodation spaces on board the ship. Domestic wastes does not include grey water.

 

2.8 Operational wastes means all solid wastes (including slurries) not covered by Annexes to MARPOL that are collected on board during normal maintenance or operations of a ship, or used for cargo stowage and handling. Operational wastes also includes cleaning agents and additives contained in cargo hold and external wash water. Operational wastes does not include grey water, bilge water or other similar discharges essential to the operation of a ship, taking into account the guidelines developed by the Organization.

 

2.9 Oil residue (sludge) means the residual waste oil products generated during the normal operation of a ship such as those resulting from the purification of fuel or lubricating oil for main or auxiliary machinery, separated waste oil from oil filtering equipment, waste oil collected in drip trays, and waste hydraulic and lubricating oils.

 

2.10 Oily rags means rags which have been saturated with oil as controlled in Annex I to MARPOL. Contaminated rags are rags which have been saturated with a substance defined as a harmful substance in Annexes to MARPOL.

 

2.11 Cargo residues means the remnants of any cargo which are not covered by Annexes to MARPOL and which remain on the deck or in holds following loading or unloading, including loading and unloading excess or spillage, whether in wet or dry condition or entrained in wash water but does not include cargo dust remaining on the deck after sweeping or dust on the external surfaces of the ship.

 

2.12 Fishing gear means any physical device or part thereof or combination of items that may be placed on or in the water or on the sea-bed with the intended purpose of capturing or controlling for subsequent capture or harvesting, marine or fresh water organisms.

 

3 MATERIALS AND MANUFACTURE

 

3.1 The materials used in the individual parts of the incinerator are to be suitable for the intended application with respect to heat resistance, mechanical properties, oxidation, corrosion, etc. as in other auxiliary marine equipment.

 

3.2 Piping for fuel and oil residue (sludge) should be seamless steel of adequate strength and to the satisfaction of the Administration. Short lengths of steel, or annealed copper nickel, nickel copper, or copper pipe and tubing may be used at the burners. The use of non-metallic materials for fuel lines is prohibited. Valves and fittings may be threaded in sizes up to and including 60 mm O.D. (outside diameter), but threaded unions are not to be used on pressure lines in sizes 33 mm O.D. and over.

 

3.3 All rotating or moving mechanical and exposed electrical parts should be protected against accidental contact.

 

3.4 Incinerator walls are to be protected with insulated fire bricks/refractory and a cooling system. Outside surface temperature of the incinerator casing being touched during normal operations should not exceed 20C above ambient temperature.

 

3.5 Refractory should be resistant to thermal shocks and resistant to normal ship's vibration. The refractory design temperature should be equal to the combustion chamber design temperature plus 20% (see paragraph 4.1).

 

3.6 Incinerating systems should be designed such that corrosion will be minimized on the inside of the systems.

 

3.7 In systems equipped for incinerating liquid wastes, safe ignition and maintenance of combustion should be ensured, e.g. by a supplementary burner using gas oil/diesel oil or equivalent.

 

3.8 The combustion chamber(s) should be designed for easy maintenance of all internal parts including the refractory and insulation.

 

3.9 The combustion process should take place under negative pressure which means that the pressure in the furnace under all circumstances should be lower than the ambient pressure in the room where the incinerator is installed. A flue gas fan may be fitted to secure negative pressure.

 

3.10 The incinerating furnace may be charged with solid waste either by hand or automatically. In every case, fire dangers should be avoided and charging should be possible without danger to the operating personnel.

 

.1 For instance, where charging is carried out by hand, a charging lock may be provided which ensures that the charging space is isolated from the fire box as long as the filling hatch is open.

.2 Where charging is not effected through a charging lock, an interlock should be installed to prevent the charging door from opening while the incinerator is in operation with burning of garbage in progress or while the furnace temperature is above 220C.

3.11 Incinerators equipped with a feeding sluice or system should ensure that the material charged will move to the combustion chamber. Such system should be designed such that both operator and environment are protected from hazardous exposure.

 

3.12 Interlocks should be installed to prevent ash removal doors from opening while burning is in progress or while the furnace temperature is above 220C.

 

3.13 The incinerator should be provided with a safe observation port of the combustion chamber in order to provide visual control of the burning process and waste accumulation in the combustion chamber. Neither heat, flame, nor particles should be able to pass through the observation port. An example of a safe observation port is high-temperature glass with a metal closure.

 

3.14 Electrical requirements1

______________________________

1 International Electrotechnical Commission (IEC) Standards, particularly IEC Publication 60092 Electrical Installations in Ships, are applicable for this equipment.

 

3.14.1 Electrical installation requirements should apply to all electrical equipment, including controls, safety devices, cables, and burners and incinerators.

 

3.14.1.1 A disconnecting means capable of being locked in the open position should be installed at an accessible location at the incinerator so that the incinerator can be disconnected from all sources of potential. This disconnecting means should be an integral part of the incinerator or adjacent to it (see paragraph 5.1).

 

3.14.1.2 All uninsulated live metal parts should be guarded to avoid accidental contact.

 

3.14.1.3 The electrical equipment should be so arranged so that failure of this equipment will cause the fuel supply to be shut off.

 

3.14.1.4 All electrical contacts of every safety device installed in the control circuit should be electrically connected in series. However, special consideration should be given to arrangements when certain devices are wired in parallel.

 

3.14.1.5 All electrical components and devices should have a voltage rating commensurate with the supply voltage of the control system.

 

3.14.1.6 All electrical devices and electric equipment exposed to the weather should meet the requirements of international standards acceptable to the Organization.2

______________________________

2 Refer to IEC Publication 60092-201, table V (1994-08 edition).

 

3.14.1.7 All electrical and mechanical control devices should be of a type tested and accepted by a nationally recognized testing agency, according to international standards.

 

3.14.1.8 The design of the control circuits should be such that limit and primary safety controls should directly open a circuit that functions to interrupt the supply of fuel to combustion units.

 

3.14.2 Overcurrent protection

 

3.14.2.1 Conductors for interconnecting wiring that is smaller than the supply conductors should be provided with overcurrent protection based on the size of the smallest interconnecting conductors external to any control box, in accordance with the requirements of international standards acceptable to the Organization.9

______________________________

3 Refer to IEC Publication 60092-202 (1994-03 edition with amendment).

 

3.14.2.2 Overcurrent protection for interconnecting wiring should be located at the point where the smaller conductors connect to the larger conductors. However, overall overcurrent protection is acceptable if it is sized on the basis of the smallest conductors of the interconnecting wiring, or in accordance with the requirements of international standards acceptable to the Organization.4

______________________________

4 Refer to IEC Publication 60092-202 (1994-03 edition with amendment).

 

3.14.2.3 Overcurrent protection devices should be accessible and their function should be identified.

 

3.14.3 Motors

 

3.14.3.1 All electric motors should have enclosures corresponding to the environment where they are located, at least IP 44, in accordance with the requirements of international

standards acceptable to the Organization.5

______________________________

5 Refer to IEC Publication 60529 (2013-08 edition with amendment).

 

3.14.3.2 Motors should be provided with a corrosion-resistant nameplate specifying information in accordance with the requirements of international standards acceptable to the Organization.6

______________________________

6 Refer to IEC Publication 60092-301 (1980-01 edition with amendment).

 

3.14.3.3 Motors should be provided with running protection by means of integral thermal protection, by overcurrent devices, or a combination of both in accordance with manufacturer's instruction that should meet the requirements of international standards acceptable to the Organization.7

______________________________

7 Refer to IEC Publication 60092-202 (1994-03 edition with amendment).

 

3.14.3.4 Motors should be rated for continuous duty and should be designed for an ambient temperature of 45C or higher.

 

3.14.3.5 All motors should be provided with terminal leads or terminal screws in terminal boxes integral with, or secured to, the motor frames.

 

3.14.4 Ignition system

 

3.14.4.1 When automatic electric ignition is provided, it should be accomplished by means of either a high-voltage electric spark, a high-energy electric spark, or a glow coil.

 

3.14.4.2 Ignition transformers should have an enclosure corresponding to the environment where they are located, at least IP 44 in accordance with the requirements of international standards acceptable to the Organization.8

______________________________

8 Refer to IEC publication 60529 (2013-08 edition with amendment).

 

3.14.4.3 Ignition cable should meet the requirements of international standards acceptable to the Organization.9

______________________________

9 Refer to IEC Publication 60092-503 (2007-06 edition with amendment).

 

3.14.5 Wiring

 

All wiring for incinerators should be rated and selected in accordance with the requirements

of international standards acceptable to the Organization.10

______________________________

10 Refer to IEC Publication 60092-352 (2005-09 edition with amendment).

 

3.14.6 Bonding and grounding

 

3.14.6.1 Means should be provided for grounding the major metallic frame or assembly of the incinerators.

 

3.14.6.2 Non-current carrying enclosures, frames and similar parts of all electrical components and devices should be bonded to the main frame or assembly of the incinerator. Electrical components that are bonded by their installation do not require a separate bonding conductor.

 

3.14.6.3 When an insulated conductor is used to bond electrical components and devices, it should show a continuous green colour, with or without a yellow stripe.

 

4 OPERATING REQUIREMENTS

 

4.1 The incinerator system should be designed and constructed for operation with the following conditions:

 

Maximum combustion chamber

 

flue gas outlet temperature

 

Minimum combustion chamber

1,200C

flue gas outlet temperature

 

Preheat temperature of

850C

combustion chamber

650C

4.2 For batch loaded incinerators, there are no preheating requirements. However, the incinerator should be designed that the temperature in the actual combustion space should reach 600C within 5 minutes after start.

 

Prepurge, before ignition:

at least 4 air changes in the chamber(s) and stack, but not less than 15 s.

Time between restarts:

at least 4 air changes in the chamber(s) and stack, but not less than 15 s.

Postpurge, after shut-off fuel oil:

not less than 15 s after the closing of the fuel oil valve.

Incinerator discharge gases:

Minimum 6% O2 (measured in dry flue gas).

4.3 Outside surface of combustion chamber(s) should be shielded from contact such that people in normal work situations will not be exposed to extreme heat (20C above ambient temperature) or direct contact of surface temperatures exceeding 60C. Examples for alternatives to accomplish this are a double jacket with an air flow in between or an expanded metal jacket.

 

4.4 Incinerating systems are to be operated with underpressure (negative pressure) in the combustion chamber such that no gases or smoke can leak out to the surrounding areas.

 

4.5 The incinerator should have warning plates attached in a prominent location on the unit, warning against unauthorized opening of doors to combustion chamber(s) during operation and against overloading the incinerator with garbage.

 

4.6 The incinerator should have instruction plate(s) attached in a prominent location on the unit that clearly addresses the following:

 

4.6.1 Cleaning ashes and slag from the combustion chamber(s) and cleaning of combustion air openings before starting the incinerator (where applicable).

 

4.6.2 Operating procedures and instructions. These should include proper start-up procedures, normal shut-down procedures, emergency shut-down procedures, and procedures for loading garbage (where applicable).

 

4.7 To avoid building up of dioxins, the flue gas should be shock-cooled to a maximum 350C within 2.5 m from the combustion chamber flue gas outlet.

 

5 OPERATING CONTROLS

 

5.1 The entire unit should be capable of being disconnected from all sources of electricity by means of one disconnect switch located near the incinerator (see paragraph 3.14.1.1).

 

5.2 There should be an emergency stop switch located outside the compartment which stops all power to the equipment. The emergency stop switch should also be able to stop all power to the fuel pumps. If the incinerator is equipped with a flue gas fan, the fan should be capable of being restarted independently of the other equipment on the incinerator.

 

5.3 The control equipment should be so designed that any failure of the following equipment will prevent continued operations and cause the fuel supply to be cut off.

 

5.3.1 Safety thermostat/draft failure

 

5.3.1.1 A flue gas temperature controller, with a sensor placed in the flue gas duct, should be provided that will shut down the burner if the flue gas temperature exceeds the temperature set by the manufacturer for the specific design.

 

5.3.1.2 A combustion temperature controller, with a sensor placed in the combustion chamber, should be provided that will shut down the burner if the combustion chamber temperature exceeds the maximum temperature.

 

5.3.1.3 A negative pressure switch should be provided to monitor the draft and the negative pressure in the combustion chamber. The purpose of this negative pressure switch is to ensure that there is sufficient draft/negative pressure in the incinerator during operations. The circuit to the program relay for the burner will be opened and an alarm activated before the negative pressure rises to atmospheric pressure.

 

5.3.2 Flame failure/fuel oil pressure

 

5.3.2.1 The incinerator should have a flame safeguard control consisting of a flame sensing element and associated equipment for shut down of the unit in the event of ignition failure and flame failure during the firing cycle. The flame safeguard control should be so designed that the failure of any component will cause a safety shut down.

 

5.3.2.2 The flame safeguard control should be capable of closing the fuel valves in not more than 4 s after a flame failure.

 

5.3.2.3 The flame safeguard control should provide a trial-for-ignition period of not more than 10 s during which fuel may be supplied to establish flame. If flame is not established within 10 s, the fuel supply to the burners should be immediately shut off automatically.

 

5.3.2.4 Whenever the flame safeguard control has operated because of failure of ignition, flame failure, or failure of any component, only one automatic restart may be provided. If this is not successful then manual reset of the flame safeguard control should be required for restart.

 

5.3.2.5 Flame safeguard controls of the thermostatic type, such as stack switches and pyrostats operated by means of an open bimetallic helix, are prohibited.

 

 

5.3.2.6 If fuel oil pressure drops below that set by the manufacturer, a failure and lock out of the program relay should result. This also applies to an oil residue (sludge) burner (applies where pressure is important for the combustion process or a pump is not an integral part of the burner).

 

5.3.3 Loss of power

 

If there is a loss of power to the incinerator control/alarm panel (not remote alarm panel), the system should shut down.

 

5.4 Fuel supply

 

Two fuel control solenoid valves should be provided in series in the fuel supply line to each burner. On multiple burner units, a valve on the main fuel supply line and a valve at each burner will satisfy this requirement. The valves should be connected electrically in parallel so that both operate simultaneously.

 

5.5 Alarms

 

5.5.1 An outlet for an audible alarm should be provided for connection to a local alarm system or a central alarm system. When a failure occurs, a visible indicator should show what caused the failure (The indicator may cover more than one fault condition.).

 

5.5.2 The visible indicators should be designed so that, where failure is a safety related shutdown, manual reset is required.

 

5.6 After shutdown of the oil burner, provision should be made for the fire box to cool sufficiently (as an example, of how this may be accomplished, the exhaust fan or ejector could be designed to continue to operate. This would not apply in the case of an emergency manual trip).

 

6 OTHER REQUIREMENTS

 

6.1 Documentation

 

A complete instruction and maintenance manual with drawings, electric diagrams, spare parts list, etc. should be furnished with each incinerator.

 

6.2 Installation

 

All devices and components should, as fitted in the ship, be designed to operate when the ship is